Internal Installation Disconnectors RV 10/630-U3

A disconnector of the internal installation with a grounding knife RV 10/630-U3 is intended for repeated switching and switching without load of sections of three-phase current circuits with a voltage of 6 (10) kV, frequency of 50 Hz. The RV 10/630-U3 disconnector is installed in complete transformer substations (CTS), one-way service cameras (OWSC), and complete distribution devices (CDD).

CONSTRUCTION AND OPERATING PRINCIPLE:

The high voltage AC disconnectors RV 10/630-U3 are intended to:

  • to disconnect and energize high voltage electrical circuits in the absence of load current or to change the connection pattern;
  • to ensure the safe operation of the disconnected area;
  • to enable and deactivate charging currents of air and cable lines, idling currents of transformers and currents of small loads.

The disconnectors are installed in AC networks at frequencies of 50 and 60 Hz at a voltage of 6(10) kV.

The RV 10/630-MC series disconnector is a three-pole vertically-cutting switching device and consists of:

  • insulated frame
  • current conducting system contacts
  • manual drive

Fixed contacts (a detachable connection and an indivisible hinged connection) made from a copper tyre are mounted on insulators mounted on a disconnection frame. A drive shaft, a grounding knife and other disconnecting elements are also mounted on the frame.

The movable contact knives are connected to fixed contacts via a hinged joint.

The necessary contact force in the hinged and detachable contact connection is achieved by means of the springs installed.

The movable contact knives are actuated by a drive shaft mounted on the disconnect frame via levers and traction insulators.

The external cables are fastened by means of bolt connections to fixed contacts.

The grounding knife is fastened to the disconnect frame by a bolted connection. The disconnector structure allows the customer to remove or add grounding knives on his own.

RV 10/630-U3 symbols:
  • R – disconnector
  • V – internal installation
  • 10 – rated voltage, kW
  • 630 – rated current, A
  • U3 – climate performance according to GOST 15150-69
CONDITIONS OF OPERATION:
  • Altitude: not more than 1,000 m.
  • Ambient temperature: from -60°C to +40°C.
  • Relative humidity: not more than 90% at 20°C.
  • Life of switch until first major maintenance: 6000 cycles of BO.
  • Duration of service: not less than 25 years.
  • Disconnect: vertical or horizontal, it is also permissible to have a disconnect in the inclined plane up to 45°.
  • Climatic conditions: MC by GOST 15150-69.
  • The switch and drive do not require the replacement of the parts for the whole life of the service life, subject to transportation, storage, installation and operation rules.
SET OF DELIVERIES:
  1. Disconnector RV 10/630-U3 – 1 pc.
  2. Manual drive MD-10 – 1 pc.
  3. Passport – 1 pc.
  4. Operating instructions – 1 pc.
Download the questionnaire

Your form has been submitted!