Complete closed-type distribution substation KRPZ Integral-35

The complete distribution substation of the closed type KRPZ Integral-35 kV is intended for distributing the electrical energy of the alternating three-phase current at a voltage of 35 kV, at a frequency of 50 Hz with insulated neutral, and the extension of cable networks to power or air lines.

CONSTRUCTION AND OPERATING PRINCIPLE:

Features of the KRPZ Integral-35 substation:

  • Block modular structure;
  • Air/cable input/output;
  • A version of a heated substation structure, a non-combustible material of a thickness of 50 to 100 mm shall be used as insulating and noise-reducing material;
  • The sub-station is equipped with heating, ventilation and air conditioning.
KRPZ INTEGRAL-35 symbols:
  1. K (К) – complete
  2. R (Р) – distibutive
  3. P (П) – substation
  4. Z (З) – closed type
  5. Integral – Equipment Distinguishing Sign
  6. 35 – rated voltage, kV
  7. Т1 (U1, UHL1, HL1) – climatic performance for the regions:
  • Tropical climates (from -100C to +500C) – T1;
  • Temperate (from -400C to +400C) – U1;
  • Temperate and cold climates (between -450C and +400C) – UHL1;
  • Cold climate (from -550C to +300C) – HL1 (insulated).
COMPLETION:

Options for the HVD configuration:

  • Fitted with vacuum or electric switches;
  • Protection devices for domestic and foreign manufacturers are used.

Options for Local Needs LVDD:

  • Transformer of own needs;
  • A closet of personal needs;
  • An operating current cabinet;
  • A central alarm cabinet;
  • Low-voltage complete devices for heating and ventilation;
  • fire alarm cabinet.
CONDITIONS OF OPERATION:
  • Altitude not exceeding 1000 m;
  • Climate performance according to GOST 15150 T1, U1, UHL1, HL1;
  • A non-explosive environment free of conductive dust, aggressive gases and vapours, which destroys metals and insulates.
BASIC TECHNICAL PARAMETERS:
NameValue
Rated voltage (linear), kV35
Maximum working voltage, kV40,5
Main circuits rated at 50 Hz, A630; 1000; 1600; 2500
Rated high voltage switch off at 50 Hz, kA20; 25; 31,5; 40; 50; 63; 80; 100
Current of electrodynamic resistance, kA51, 81
Current of thermal resistance, kA20; 25; 31,5; 40
Test voltage of industrial frequency, kV85,5
Rated power of power transformers, kVA25; 40; 63
Rated voltage of auxiliary circuits, V:
- AC control and signalling protection circuits=110, =220, ~220
- voltage transformer chains (protection, measurement, accounting)~100
- light circuits inside cells~36
- light circuits inside the substation~220
GOST isolation levelnormal
Insulation typeair/combined
Insulation of electrically conductive tyreswith insulated collar
Degree of protection under GOST 14254-96
- KRPZ INTEGRALIP43
- Built-in equipment (open door)IP10